产品简介Increase the safety and speed of indoor and outdoor electrical thermography with these UL and CSA certified IR Windows. These IR Windows come in three diameters: 2", 3" or 4".
产品概述 With a Kwik Twist cover that magnetically sticks to the panel when removed, Fluke IR Windows are easy to use and deliver unmatched image clarity through a CLIRVU® crystal. Exclusive to Fluke IR Windows, CLIRVU crystal technology is impervious to both moisture and vibration. CLIRVU crystals are designed to withstand the extreme pressures and temperatures of an arc-fault event, and offer protection from molten projectiles associated with arc-flashes.
Engineered and tested to withstand electric-arcs up to 50 kA for30 cycles.
Certified by UL & CSA for Type 3/12 (Outdoor) environments in North America, these C-Range windows are tested to withstand the long term aging effects of UV exposure.
Certified by SIRA Certification IP65 (Outdoor) environments in Europe.
The CLIRVU® coating—exclusive to Fluke IR Windows—seals the optic prior to assembly to protect against moisture degradation.
Own a Fluke Camera? The Quadraband™ optic is IR-Fusion® compatible, allowing the thermographer to see potential problems in visual light and thermographic mode.
Got more than one window per panel? Each C-Range window is delivered with an identification plate attached for unique, on-site numbering for rapid location confirmation and faster repairs.
Each infrared window comes complete with a security access key, installation instructions and self-adhesive drilling template.
Detailed Specifications |
Optic data |
Crystal insert diameter |
3460346 FLK-050-CLKT: |
50 mm (1.97 in) |
3460387 FLK-075-CLKT: |
75 mm (2.96 in) |
3460439 FLK-100-CLKT: |
100 mm (3.94 in) | |
Viewing aperture diameter |
3460346 FLK-050-CLKT: |
43 mm (1.7 in) |
3460387 FLK-075-CLKT: |
68 mm (2.7 in) |
3460439 FLK-100-CLKT: |
89 mm (3.5 in) | |
Viewing aperture area |
3460346 FLK-050-CLKT: |
1452 mm2 (2.25 sq in) |
3460387 FLK-075-CLKT: |
3632 mm2 (5.63 sq in) |
3460439 FLK-100-CLKT: |
6322 mm2 (9.79 sq in) | |
Thickness |
3460346 FLK-050-CLKT: |
2 mm (0.08 in) |
3460387 FLK-075-CLKT: |
2 mm (0.08 in) |
3460439 FLK-100-CLKT: |
4 mm (0.16 in) | |
CLIRVU coating |
3460346 FLK-050-CLKT: |
Yes |
3460387 FLK-075-CLKT: |
Yes |
3460439 FLK-100-CLKT: |
Yes | |
Shortwave IR capable |
3460346 FLK-050-CLKT: |
Yes |
3460387 FLK-075-CLKT: |
Yes |
3460439 FLK-100-CLKT: |
Yes | |
Midwave IR capable |
3460346 FLK-050-CLKT: |
Yes |
3460387 FLK-075-CLKT: |
Yes |
3460439 FLK-100-CLKT: |
Yes | |
Longwave IR capable |
3460346 FLK-050-CLKT: |
Yes |
3460387 FLK-075-CLKT: |
Yes |
3460439 FLK-100-CLKT: |
Yes | |
Ultraviolet (UV) capable |
3460346 FLK-050-CLKT: |
Yes |
3460387 FLK-075-CLKT: |
Yes |
3460439 FLK-100-CLKT: |
Yes | |
Visual capable |
3460346 FLK-050-CLKT: |
Yes |
3460387 FLK-075-CLKT: |
Yes |
3460439 FLK-100-CLKT: |
Yes | |
Fusion capable |
3460346 FLK-050-CLKT: |
Yes |
3460387 FLK-075-CLKT: |
Yes |
3460439 FLK-100-CLKT: |
Yes | |
Underwriters Laboratories (UL) recognized |
Yes |
UL50 environmental |
|
UL746C |
|
UL94 |
|
Canadian Standards Association (CSA) approval |
Yes |
Environmental |
|
KEMA (Arc-Testing) |
ANSI C37.20.7 |
|
50 kA for 30 cycles @60 Hz | |
EEMACS 14-1 Type-B |
|
40 kA for 30 cycles @60 Hz | |
ASTA (Arc-Testing) |
IEC 62271 |
|
20 kA for 5 cycles @50 Hz | |
TUV |
Cyclic humidity withstand |
|
Vibration withstand |
|
NEMKO |
Resistance of insulating materials to 100° |
|
Resistance of insulating material to ball pressure (Brinell) |
|
Glow-wire test 650 °C |
|
Lloyds Register |
Up to 11 kV marine switchgear, indoor or outdoor |
|
General Specifications |
Maximum temperature |
Gaskets: |
250 °C (482 °F) |
Body: |
659 °C (1219 °F) |
Optic: |
1400 °C (2552 °F) | |
Gaskets |
|
Low smoke and fume (LSF) compliant silicone | |
IP rating |
|
NEMA rating |
|
Type 3/12 (UL and CSA Third Party Certified) | |
Vibration rating |
|
Humidity rating |
|
Pull-out strength |
|
Warranty |
|
Lifetime replacement against | |
|